Liebert Power Supply PowerSure Personal User Manual

POWERSURE™ PERSONAL  
300-500 VA  
115V  
USER MANUAL  
English  
 
INTRODUCTION & SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert PowerSure Personal  
Uninterruptible Power System (UPS).  
It provides conditioned power to  
microcomputers and other sensitive electronic equipment.  
NOTE: This equipment has been tested and found to comply with the limits for a  
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are  
designed to provide reasonable protection against harmful interference in a  
residential installation. This equipment uses, generates and can radiate radio  
frequency energy and, if not installed and used in accordance with the  
instructions, may cause harmful interference with radio communications.  
However, there is no guarantee that interference will not occur in a particular  
installation. If this equipment does cause harmful interference to radio or  
television reception, which can be determined by turning the equipment off and  
on, the user is encouraged to try to correct the interference by one or more of the  
following measures:  
-
-
-
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and the receiver.  
Connect the equipment into an outlet on a circuit different from that which  
the receiver is connected.  
-
Consult the dealer or an experienced radio/TV technician for help.  
MAJOR COMPONENTS  
TM  
PowerSure  
Personal  
DB-9 Interface for  
SiteNet MultiLink Cable  
Utility / Battery LED  
Warning LED  
Power ON / Standby  
Output  
Receptacles  
Input Receptacle  
Fuse Holder  
R
Liebert  
BACK  
FRONT  
 
TM  
PowerSure Personal  
Line Diagram  
INPUT  
L
OUTPUT  
L
TVSS and  
EMI / RFI  
Filters  
Transfer  
Switch  
Battery  
Battery  
Charger  
Inverter  
N
G
N
G
Normal Operation  
During normal operation, incoming utility power is supplied to the load as shown  
above. The utility power passes through the EMI/ RFI filters and TVSS circuitry  
and then through the transfer switch to the connected loads. The battery charger  
is operational whenever AC power is supplied, even when the unit is switched  
off. PowerSure Personal continuously monitors the batteries.  
Transfer Switch  
In Normal mode the transfer switch passes utility AC power to the connected  
load. When input utility or frequency is outside acceptable limits, the transfer  
switch activates and transfers the UPS to battery.  
Battery Charger  
In normal operation, the battery charger converts utility AC power into regulated  
DC power to float charge the battery.  
Battery  
The PowerSure Personal utilizes valve regulated, nonspillable, lead acid battery.  
At typical room temperatures and with the UPS float charging, the battery system  
will last many years.  
Transient Voltage Surge Suppression (TVSS) & EMI / RFI Filters  
These UPS components provide surge protection and filter electromagnetic  
interference (EMI) and radio frequency interference (RFI). They minimize any  
surges or interference present in the utility line and keep the sensitive equipment  
protected.  
4
 
GENERAL INSTALLATION  
T
M
PowerSure  
Personal  
T
M
PowerSure  
Personal  
R
Liebert  
R
Liebert  
Check for Damage  
Remove from Box  
T
M
PowerSure  
Personal  
4 Inches  
110 mm  
32° - 104° F  
0° - 40° C  
R
Liebert  
Plug in Loads  
T
M
PowerSure  
Personal  
T
M
PowerSure  
Personal  
R
R
Liebert  
Liebert  
Plug UPS into AC  
Press ON Button  
for 2 seconds  
5
 
MAINTENANCE  
The PowerSure Personal UPS requires very little maintenance. The batteries  
are valve regulated, nonspillable, lead acid, and require that they be kept  
charged to obtain their designed life. The UPS continuously charges the  
batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is recommended to plug in the  
UPS for at least 24 hours every four to six months to ensure full recharge of the  
batteries.  
FUSE REPLACEMENT PROCEDURES  
AC Inlet  
Insert flat blade screw  
driver into slot and pull  
fuse holder out to remove  
Fuse Holder  
Input Fuse  
Spare Fuse  
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the  
input cord from the AC input power supply and from the UPS.  
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and  
pulling out as indicated in the figure above.  
2. Remove the input fuse.  
3. Remove the spare fuse from its position by using the screwdriver to push it  
out.  
4. Place spare fuse in the input fuse position, and replace the fuse holder. The  
fuse holder will lock into position.  
5. Reconnect the input power lead to the UPS, and the input power lead to the  
input AC supply.  
6. Restart the UPS. The UPS is ready for normal operation.  
Personal Model #  
PSP300-115  
Fuse Type  
5A / 125V  
6A / 125V  
PSP500-115  
6
 
COMMUNICATIONS  
The PowerSure™ Personal UPS contains a standard DB-9 receptacle located on  
the rear of the UPS unit. Several signals are provided on this port and are  
assigned as follows:  
PIN  
1
2
ASSIGNMENT DESCRIPTION  
Low Battery (open collector)  
No connection  
3
No connection  
4
5
6
7
On Battery Mode Shutdown (5-12 DC)  
On Battery Mode Shutdown Return  
Utility Fail / Normally On (open collector)  
Low Battery (open emitter)  
8
9
Utility Fail (common) (pins 6 & 9)  
Utility Fail / Normally Off (open collector)  
Pin Assignment  
Collector to Emitter*  
Open Collector  
(+)  
(-)  
Open Emitter  
*Maximum voltage and current on pins 1, 6, 7, 8, 9 is 60V DC; 5.0 mA.  
7
 
TROUBLESHOOTING  
If the UPS fails to operate properly, turn off the unit and repeat the steps in the  
installation section of this manual. If the problem persists, refer to the chart  
below:  
PROBLEM  
CAUSE  
SOLUTION  
UPS will not start  
Overload/Short Circuit  
Check fuse at rear of UPS. If blown, replace it  
and restart the UPS. For further help, call your  
Liebert representative  
UPS starts on  
battery, but will  
not switch to AC  
UPS not plugged in  
Fuse blown  
Plug in power cord securely  
Replace fuse and restart UPS  
Call a qualified electrician  
Power not available at  
utility receptacle  
Input voltage below  
threshold  
Wait until voltage rises to appropriate level  
Voltage must be higher than 90 VAC  
AC overvoltage  
AC voltage must be less than 132 VAC  
UPS shuts down  
Overload/Short Circuit  
Check the fuse holder at rear of UPS. If fuse is  
blown, replace it and restart the UPS. If problem  
persists, disconnect some of the equipment from  
your UPS - the total wattage of your equipment  
may exceed the capacity of the UPS. For  
further help, call your Liebert representative  
Low Battery  
Turn OFF equipment and recharge UPS battery  
for at least 7 to 10 hours. If problem persists,  
contact your Liebert representative  
Sitenet 1 Shutdown  
Consult the Sitenet 1 User Manual or contact  
your LAN administrator  
8
 
LED & ALARM INDICATIONS  
Startup  
Mode  
Green  
Red  
Alarm  
Action  
Press ON  
button for  
2 seconds  
Flash  
1-2 sec.  
Flash  
1-2 sec.  
Beep  
1-2 sec.  
UPS Start  
AC Mode  
Mode  
Green  
ON  
Red  
OFF  
Flash 10 sec.  
every 4 min.  
Flash every  
0.5 sec  
Alarm  
OFF  
Flash 10 sec.  
every 4 min.  
2 Beeps every  
0.5 sec  
Indicates  
UPS is on-line  
Battery  
Fault  
Reduce loads  
AC Normal  
Check Battery  
Overload  
ON  
ON  
Continuous  
Beep  
UPS Fault  
ON  
ON  
UPS Failure  
Battery Mode  
Mode  
Green  
Flash  
every 3 sec  
Flash  
every 3 sec  
Flash  
Red  
Alarm  
Beep  
every 3 sec  
Continuous  
Beep  
Indicates  
UPS is on  
Battery  
Back Up  
OFF  
UPS Fault  
ON  
OFF  
OFF  
No Output  
Low Battery  
Warning  
Low Battery  
Shutdown  
Overload  
Warning  
Beep  
every 0.5 sec  
UPS is about  
to shutdown  
UPS  
every 0.5 sec  
Flash  
5 sec  
Flash  
Beep  
5 sec  
2 Beeps  
every 0.5 sec  
Continuous  
Beep  
Shutdown  
Flash  
every 0.5 sec  
Reduce loads  
every 3 sec  
Overload  
Shutdown  
Reduce loads  
& restart  
OFF  
ON  
Shutdown  
Mode  
Green  
Red  
Alarm  
Action  
Press ON  
button for  
2 seconds  
UPS  
Shutdown  
OFF  
OFF  
OFF  
9
 
115V SPECIFICATIONS  
Model Number  
PSP300-115  
300 / 180  
PSP500-115  
500 / 300  
Model Rating VA / W  
DIMENSIONS: in (mm)  
Unit H x W x D  
7.0 x 3.0 x 9.4  
(178 x 76 x 238)  
10.6 x 4.3 x 12.3  
(270 x 110 x 312)  
7.0 x 3.0 x 9.4  
(178 x 76 x 238)  
10.6 x 4.3 x 12.3  
(270 x 110 x 312)  
Shipping H x W x D  
WEIGHT: lbs (kg)  
Unit  
Shipping  
6.2 (2.8)  
7.7 (3.5)  
8.0 (3.6)  
9.5 (4.3)  
INPUT AC PARAMETERS  
Voltage Range  
90-132 VAC  
without Battery Operation  
Low Line Transfer  
High Line Transfer  
Frequency  
90 VAC  
132 VAC  
45-55 Hz or 54-66 Hz; auto sensing  
Input Power Cord  
6 ft. detachable, w/ NEMA 5-15 P  
OUTPUT AC PARAMETERS  
Output Receptacles  
Voltage (Battery Mode)  
Output Current  
(4) 5-15R  
115 VAC + 5%  
2.6 A  
4.3 A  
Waveform (Battery Mode)  
Frequency  
Stepped Sinewave  
50 Hz or 60 Hz; auto sensing  
Overload Warning  
101 – 120%  
(Utility and Battery Modes)  
Overload Shutdown  
(Utility and Battery Modes)  
Overload Warning  
+ (15 – 25 W)  
Overload Warning  
+ (20 – 45 W)  
BATTERY PARAMETERS  
Type  
Valve-regulated, nonspillable, lead acid  
(1) x 12V x 4.5 Ah  
Quantity x Voltage x  
Rating  
(1) x 12V x 7.0 Ah  
Approved Battery  
Manufacturers:  
Transfer Time  
Back-up Time:  
Full load  
CSB, Panasonic, BB Battery, and Yuasa  
2 – 6 ms typical  
At 77°F (25°C), resistive loading, with fully charged batteries:  
> 4 minutes  
12 minutes  
Half load  
Recharge Time  
7-10 hours to 90% capacity, after full discharge into 100% resistive  
load  
ENVIRONMENTAL  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Elevation  
Audible Noise  
+32° F to + 104° F (0° C to +40° C)  
+5° F to + 122° F (-15° C to +50° C)  
0% to 90%, non-condensing  
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating  
< 40 dBA, at 1 meter  
AGENCY  
Safety  
UL 1778, c-UL Listed  
Surge  
IEEE C62.41 Category A  
ESD  
IEC 801-2, Level 3, Criterion< 2  
IEC 801-3, Level 3, Criterion< 2  
IEC 801-4, Level 4, Criterion< 2  
Susceptibility  
Electrical Fast  
Transient/Burst  
Emissions  
FCC Part 15, Subpart B, Class B  
ISTA Project 1A  
Transportation  
10  
 
LIMITED WARRANTY  
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser  
and to its customer (collectively referred to as the "Purchaser"): the enclosed  
Uninterruptible Power System (UPS) and components are free from defects in  
materials and workmanship under normal use, service, and maintenance FOR A  
PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from  
Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE  
ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED, EXPRESS  
OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR  
FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not  
applicable to consumer products acquired by individuals and used for personal,  
family, or household purposes (as distinguished from industrial or other purposes).  
Local laws may not allow limitations on how long an implied warranty lasts, so the  
above limitation may not apply to you. This warranty gives you specific legal rights,  
and you may have other rights which vary according to local law.  
Certain repairs or services are the responsibility of the Purchaser and the Purchaser  
is expected to pay for them. This warranty does not extend either to products with  
removed or altered serial numbers or to any losses or damages due to act of God or  
source external to the product, misuse, accident, abuse, neglect, negligence,  
unauthorized modification, alteration, or repair, use beyond rated capacity, or  
improper installation, maintenance, application or use, including, without limitation,  
use in a manner contrary to the accompanying instructions or applicable codes.  
WARNING: Warranty is void if the battery is allowed to discharge below the minimum  
battery cutoff point. To prevent such discharge DO NOT leave the unit power switch  
"ON" for more than two (2) days without AC power being supplied to the UPS. The  
battery must be recharged every four (4) to six (6) months when not in use.  
If the UPS fails to conform with the above warranty within the two year warranty  
period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or  
replacements are warranted for the remainder of the original warranty period. To  
make a warranty claim, purchaser should call a Liebert Representative to obtain a  
Returned Goods Authorization number and shipping instructions. Return  
transportation costs to Liebert are the responsibility of the Purchaser.  
"LIFE SUPPORT" POLICY  
This product is not recommended, and the Company will not knowingly sell this  
product, for use with life support and other designated "critical" devices. ANY SUCH  
USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL  
WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY,  
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND  
EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY  
AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES  
THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL  
OR INDIRECT DAMAGES.  
11  
 
POWERSURE™ PERSONAL  
300- 500 VA  
115V  
Technical Support  
U.S.A.  
1-800-222-5877  
Outside the U.S.A.  
+1 614-841-6755  
+44 1628 403 200  
+33 1 4 360 26 19  
+49 21669649340  
+39 2 98250 1  
+00 31 475 504050  
+614-841-5471  
U.K.  
France  
Germany  
Italy  
Netherlands  
E-mail  
Web site  
Worldwide FAX tech support  
The Company Behind The Products  
With more than 500,000 installations around  
the globe, Liebert is the world leader in  
While every precaution has been taken  
to ensure accuracy and completeness of  
this literature, Liebert Corporation  
computer protection systems.  
Since its  
founding in 1965, Liebert has developed a  
complete range of support and protection  
systems for sensitive electronics:  
assumes  
no  
responsibility,  
and  
disclaims all liability for damages  
resulting from use of this information or  
for any errors or omissions.  
Environmental systems: close-control air  
conditioning from 1.5 to 60 tons.  
Power conditioning and UPS with power  
ranges from 250 VA to more than 1000 kVA.  
© 2001 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without  
notice.  
Integrated  
systems that provide both  
environmental and power protection in  
single, flexible package.  
a
®
Liebert and the Liebert logo are  
registered trademarks of Liebert  
Monitoring and control — on-site or remote —  
from systems of any size or location  
Service and support, through more than 100  
service centers around the world, and a 24-  
hour Customer Response Center.  
Corporation. All names referred to are  
trademarks or registered trademarks of  
their respective owners.  
SL-23265 (2/01) Rev. 2  
12  
 

Leviton Network Router Internet Gateway User Manual
LG Electronics Cell Phone UX700W User Manual
LG Electronics Washer WM2101H User Manual
Linksys Network Router WRT120N User Manual
LL Bean Weather Radio 0FHF4 User Manual
Lochinvar Water Heater SSS03 User Manual
Logitech Headphones 350vi User Manual
Makita Power Screwdriver 6094D User Manual
Makita Power Screwdriver 6800DBV User Manual
Makita Trash Compactor 4399D User Manual